2
Advant Controller 31 / Issued: 03.99
Hardware 07 KP 90 R303
8 .1
The RCOM protocol is compatible with MP200/1 with
DSCA 180A. All RCOM services are available (cold
start, warm start, normalization, clock synchronization,
write data, read data, event polling).
The RCOM interface for connection of the modem
complies with EIA RS-232. It can also be used as an
EIA RS-485 interface.
An additional operator interface (CONSOLE) comply-
ing with EIA RS-232 is provided as a commissioning
aid (indication of the communication sequence, plan-
ning telephone numbers etc.)
Software clock; time can be used in the PLC program.
Differences between RCOM and RCOM+, see volume
3, chapter 2.6.
All other features of RCOM which are not mentioned
in the chapter “Differences” apply correspondingly for
RCOM+.
The connection element RCOM+ can be used with the
communication module 07 KP 90 from index b up.
1.3 Planning with the 907 KP 90 R202
software package
The communication sequence is planned with connec-
tion elements contained in the 907 KP 90 R202 docu-
mentation and software package (see also Ordering in-
formation). This package also contains the manual for the
RCOM 07 KP 90 R303 communication module and plan-
ning examples.