Advant Controller 31 / Issued: 03.99
Hardware 07 KP 90 R303
8 .1
1.5.4 Serial interfaces
Serial interface CONSOLE
A terminal (e.g. an IBM-PC with 907 PC 33 in Terminal
mode) can be connected to the CONSOLE interface for
commissioning. The CONSOLE interface can be used to
• configure the telephone directory or configure data
(only in the case of dial-up modems),
• follow the communication sequence (faultfinding dur-
ing commissioning). This function can be deactivated
after commissioning.
Serial interface RCOM
The RCOM network is connected to this interface. It is
connected via a modem with standard interface.
Serial interface CONSOLE: Terminal assignment
Interface standard: EIA RS-232
5
G
9
15
8
1
CONSOLE
G Housing Protective Ground (Shield)
1 PGND Protective Ground (Shield)
2 TxD Transmit Data (Output) (EIA RS-232)
3 RxD Receive Data (Input) (EIA RS-232)
4 RTS Request To Send (Output) (EIA RS-232)
5 CTS Clear To Send (Input) (EIA RS-232)
6 NC *
7 SGND Signal Ground (0V) (EIA RS-232)
8
to
15 not connected
* NC not connected, this pin must not be connected.
Fig. 7: Terminal assignment of the serial interface CONSOLE
G Housing Protective Ground (Shield)
1 PGND Protective Ground (Shield)
2 TxD Transmit Data (Output) (EIA RS-232)
3 RxD Receive Data (Input) (EIA RS-232)
4 RTS Request To Send (Output) (EIA RS-232)
5 CTS Clear To Send (Input) (EIA RS-232)
6 NC *
7 SGND Signal Ground (0V) (EIA RS-232)
8 not connected
9 not connected
10 RxD-P, TxD-P Receive Data (Input) (EIA RS-485)
11 RxD-N, TxD-N Receive Data (Input) (EIA RS-485)
12
to
15 not connected
* NC not connected this PIN must not be connected
Fig. 8: Terminal assignment of the serial interface RCOM
Serial interface RCOM: Terminal assignment
Interface standard: EIA RS-232 or EIA RS-485
RCOM
6
G
9
15
8
1