Advant Controller 31 / Issued: 07.99
1 Hardware 07 MK 92 R1161
8 .2
Contents
1.1 Brief description................................................. 1
1.2 Structure of the front panel elements ................. 2
1.3 Electrical connection.......................................... 3
1.3.1 Application example .......................................... 3
1.3.2 Connecting the supply voltage ........................... 5
1.3.3 Electrical isolation and earthing instructions ...... 5
1.3.4 Serial interfaces................................................. 7
1.3.5 Networking interface........................................ 10
1.4 Diagnosis .........................................................11
1.5 Programming and test software 907 MK 92......11
1.6 Technical data ................................................. 12
1.7 System cables ................................................. 15
1.8 Memory areas in 07 MK 92.............................. 18
1.9 LED control ..................................................... 18
1.10 Allocation of the ports ...................................... 18
1.1 Brief description
The 07 MK 92 R1161 communication module is a freely
programmable interface module with 4 serial interfaces.
The communication module allows external units to be
connected to the Advant Controller 31 system via a serial
interface.
The communications protocols and transmission types
can be freely defined by the user.
Programming is performed on a PC with the program-
ming and test software 907 MK 92.
1 Communication module 07 MK 92 R1161
Connecting external units
Fig. 1: Communication module 07 MK 92 R1161
Serial Comm. Processor
Advant Controller 31
07 MK 92
RUN
ERR
Supp.
2
3
4
1
LED
The communication module is connected to AC31 basic
units via the networking interface, e.g. 07 KR 91 R353,
07 KT 92 (index i onwards) 07 KT 93 or 07 KT 94.
The most important features of the communication modu-
le are:
• 4 serial interfaces:
– 2 of them are serial interfaces, optionally con-
figurable in accordance with EIA RS-232 or
EIA RS-422 or EIA RS-485 (COM3, COM4)
– 2 of them are interfaces in accordance with
EIA RS-232 (COM5, COM6)
• Freely programmable with a comprehensive function
library
• Communication with AC31 basic unit via connection
elements
• Configurable LEDs for diagnosis
• Programming and testing on a PC via COM3
• Saving applications in a Flash EPROM
Processing of the serial interfaces and the networking in-
terface is provided for in an applications program.
Programming is in the standard language ”C”.
The exchange of data between the serial communication
module and the AC31 basic unit is realized by connection
elements in the basic unit.
Komentáře k této Příručce