Advant Controller 31 / Issued: 07.99
9 Hardware 07 KP 93 R1161
8 .3
1.5 Technical data
In general, the details in section 1 System data and system structure of volume 2 of the system description Advant
Controller 31 apply as technical data. Supplementary and deviating data is listed below.
1.5.1 General data
Number of serial interfaces 2
Number of parallel interfaces 1 networking interface for connecting to the
Advant Controller 31 basic unit
Diagnosis 4 LEDs: LED1...LED4
Operating and error displays 3 LEDs: RUN, ERR, Supply
Conductor cross section
for the removable terminal blocks max. 2.5 mm
2
1.5.2 Supply voltage for 07 KP 93 R1161
Rated supply voltage 24 V DC
Power dissipation typ. 2.5 W (max. 5W)
Max. current consumption
with rated voltage 210 mA
with supply voltage 30 V 170 mA
Protection against reversed terminal connection yes
1.5.3 Connection serial interface COM3, COM4
Interface standard EIA RS232 or EIA RS485
Electrical isolation yes, interfaces with respect to each other and with
respect to the rest of the unit (also see Figure 5)
Terminal assignment and
description of the interfaces COM3, COM4 see page 6
1.5.4 LED displays
Supply 1 green LED
ERR 1 red LED
RUN 1 green LED
LED1...LED4 4 yellow LEDs
description see chapter 1.4 Diagnosis