Chapter 2 Specification of Communication port for CPU module
2 – 23
[Sample 4]
Network consists of two EHV-CPUs as follows, and the Control Editor sets the ASR communication. The setting
information of two EHV-CPUs is as follows.
16-word data from WR0 to WRF of EHV-CPU5 is transmitted from EHV-CPU5 to EHV-CPU6. In EHV-CPU6, the
received data is stored in WR0 to WRF.
EHV-CPU6
(Passive, Receive)
EHV-CPU5
(Active, Send)
Data sending
Figure 2.23 Connection diagram of Sample 4
Table 2.13 Setting information of Sample 4
Setting EHV-CPU5 EHV-CPU6
1 IP address 192.168.0.101 192.168.0.102
2 Port No. 4000 4000
3 Protocol UDP/IP, Specified UDP/IP, Specified
4 Send / Receive Send Receive
5 Access points – IP address 192.168.0.102 192.168.0.101
6 Access points – Port No. 4000 4000
7 Send Timing Cyclic sending: 40ms
8 Transmission area WR0 to WRF
9 Receiving area WR0 to WRF
[Description of sample program]
ASR port is opened in two seconds later after RUN of EHV-CPU5. If there is a communication target is on the
network (there is a response to ARP packet), the transmission is executed automatically. And similarly, EHV-CPU6
executes the receiving if the ASR port is opened in EHV-CPU6 because the ASR port is opened also in two seconds
after RUN of EHV-CPU6.